某客户高供高计三相三线电能电表,其接线方式为:Uuv—Iu、Uwv—Iw,w相电流接反,试画出其错误接线相量图,并计算更正系数?
错误接线时功率为P′:
P′=UuvIucos(30°+φ)+ Uwv(-Iw)cos(150°+φ)
=UIcos(30°+φ)-UIcos(30°-φ)
=UI[(cos30°cosφ-sin30°sinφ)-(cos30°cosφ-sin30°sinφ)]
=-UIsinφ
更正系数为: